Fire Endurance of Fiber-Reinforced Polymer-Confined Concrete Columns

By Bisby, Luke A,Kodur, Venkatesh K R,Green, Mark F
Publication: ACI Structural Journal
Date: Tuesday, November 1 2005
HEADNOTE

The use of fiber-reinforced polymers (FRPs) for strengthening and rehabilitating reinforced concrete structures has been the subject of numerous research projects and has seen widespread implementation in recent years. Very little information is available on the behavior

of FRP materials at high temperatures, however, and this is a primary factor discouraging the widespread application of FRP wraps in buildings where fire-related issues are critical design requirements. This paper presents the results of two full-scale fire endurance tests on circular FRP-wrapped reinforced concrete columns insulated with different thicknesses of fire insulation. Test data are compared with the predictions of a numerical fire simulation model, and the model is shown to adequately predict the observed thermal and structural response. It is demonstrated that, while currently available infrastructure composites are particularly sensitive to elevated temperatures, appropriately designed FRP-wrapped reinforced concrete columns are capable of achieving the required fire endurances.

Keywords: confinement; fibers; fire endurance; rehabilitation; reinforcement; strength.

INTRODUCTION

Confinement of reinforced concrete columns by circumferential wrapping with fiber-reinforced polymer (FRP) sheets is now widely recognized for its ease of application and effectiveness (Bisby et al. 2002). This technique can be used to increase both the strength and ductility of concrete columns, and has seen recent widespread use for rehabilitation, repair, strengthening, and seismic upgrading of concrete structures. If FRP materials are to be used for confinement of concrete in building and other applications, then the ability of FRP materials and FRP-confined concrete members to withstand fire must be ascertained, and rational procedures to design for fire safety must be formulated. Fire endurance tests conducted by Blontrock, Taerwe, and Vandevelde (2000, 2001) on carbon FRP-plated reinforced concrete beams and slabs indicated that externally bonded FRP materials perform poorly during fire, and thermal insulation of the FRP reinforcement is required to prevent instantaneous loss of effectiveness upon exposure to fire.

RESEARCH SIGNIFICANCE

Currently, there is no information available on the behavior of loaded FRP-wrapped reinforced concrete columns during fire. This paper presents the results of two full-scale fire tests on circular FRP-wrapped reinforced concrete columns, conducted as part of a larger study investigating the fire endurance of FRP reinforcing systems, and uses the data obtained to validate a previously presented numerical model that can be used to predict the fire endurance of these members (Bisby 2003).

BACKGROUND

FRP materials are extremely sensitive to the effects of elevated temperatures, and severe deterioration in mechanical properties, bond properties, or both can be expected at temperatures approaching the glass transition temperature Tg of the polymer adhesive/matrix (Bisby 2003; Blontrock, Taerwe, and Matthys 1999). Furthermore, all organic polymer matrix materials are combustible and will burn when subjected to a sufficiently high heat. Commonly used matrix materials such as polyester, vinyl ester, and epoxy not only support combustion, but evolve large quantities of dense black smoke (Sorathia, Dapp, and Beck 1992). Thus, there are a number of concerns, both environmental (smoke generation, toxicity) and structural (loss of strength, stiffness) associated with the use of FRP as external reinforcement for concrete members in buildings (Kodur 1999). In the current paper, the focus is on the structural behavior of FRP-wraps during fire, and the consequences of FRP degradation at high temperatures on the fire endurance of FRP-wrapped reinforced concrete columns. Detailed discussions on the deterioration of strength and stiffness of FRP materials at elevated temperatures is presented by Bisby et al. (2002) and Kodur and Baingo (1998).

Design for fire safety

Design for fire safety is concerned primarily with the protection of human life and property during fire (Lie 1992). Thus, one of the primary goals of structural fire engineering is to ensure prevention of structural collapse, at least until all building occupants have had the opportunity to safely evacuate. For building columns, structural fire endurance criteria in North America are defined exclusively in terms of load-bearing capacity because columns do not generally perform fire separation or fire barrier functions (Lie 1992). Columns are essentially required to retain sufficient strength to carry their presumed working (service) load for the required duration during exposure to a standard fire.

While the fire endurance of conventional reinforced concrete columns is generally satisfactory, when a column is strengthened with a circumferential FRP wrap (that is, its axial load capacity is increased), then there is a serious concern that loss of effectiveness of the FRP wrap during fire could lead to sudden collapse under increased service loads. For this reason, ACI 440.2R-02 (ACI Committee 440 2002) requires that FRP wraps be designed under the assumption that they are completely lost during fire. This requirement is based on conservative assumptions and is not founded in research. Furthermore, such a requirement is potentially restrictive when FRPs are contemplated for use in buildings. The engineering community often requires design recommendations developed based on the results of full-scale fire endurance tests (Munley and Dolan 2001) such as those presented in this paper.

Fire endurance criteria for FRP-wrapped columns

For the purposes of the current study, three fire endurance failure criteria, only one of which is currently recognized by ASTM E 119, have been defined. An FRP-wrapped column can be assumed to have failed if one of the three following criteria is met: 1) the column can no longer carry its full unfactored working (service) load; 2) the temperature at the FRP-concrete interface (the bond-line) exceeds the Tg of the FRP polymer adhesive/matrix; or 3) the temperature at the outside surface of the FRP exceeds the ignition temperature of the FRP material.

The first of the aforementioned criterion is essentially the currently enforced ASTM E 119 fire endurance failure criterion for columns. The second and third criteria have both been suggested recently as potential failure criteria to be used in evaluating the fire endurance of FRP-wrapped columns for use in buildings. The rationale behind the second failure criterion is that the maintenance of the FRP temperature below the matrix T^sub g^ ensures that the FRP will retain some structural effectiveness. The third criterion has been proposed to address concerns regarding the potential for increased flame spread and smoke generation when combustible FRP materials are used in external reinforcing applications. All three failure criteria are discussed in detail in subsequent sections.

FIRE TEST PROGRAM

Specimens

As part of the experimental program, two full-scale FRPwrapped and insulated circular reinforced concrete columns were tested in the column furnace of the National Research Council of Canada (NRCC). Dimensions and reinforcement details for the columns were as given in Fig. 1. Both columns had a diameter of 400 mm and an overall height of 3810 mm. The columns were reinforced internally with eight 20 mmdiameter deformed steel bars longitudinally, and a 10 mmdiameter deformed steel spiral with a center-to-center pitch of 50 mm. The concrete cover to the principal reinforcement was 50 mm. Large steel plates, 38 mm thick, were welded to the longitudinal reinforcing bars at both ends of the columns such that they could be bolted to the load heads of the column furnace test frame.

Concrete

Both columns were fabricated using carbonate aggregate concrete incorporating Type 1 normal portland cement. The coarse and fine aggregates consisted of crushed limestone with a maximum aggregate size of 14 mm, and siliceous sand, respectively. The 28-day compressive strength of the concrete was 39 MPa, and the concrete strengths at the time of testing were 39 and 40 MPa for Columns 1 and 2, respectively. The volumetric moisture content at the time of testing was estimated, using procedures outlined in ULC S101 (CAN/ULC 1989), to be approximately 8% in both cases.

Reinforcing steel

Both the longitudinal and spiral reinforcement conformed to CSA Standard G30.18, with minimum yield strengths of 400 MPa. The actual tested yield strengths of the reinforcement were 400 and 460 MPa for the spiral and longitudinal steels, respectively.

Casting, curing, and conditioning

The columns were placed vertically in a single lift, with concrete supplied by a local concrete plant. The concrete was rod-vibrated during each lift to ensure excellent consolidation. The columns were cured in a humidified plastic enclosure at 21 to 24 ?C and 100% relative humidity for 7 days, at which point the formwork was removed. The columns were subsequently conditioned in the Structures Testing Lab at Queen's University, at ambient temperature and relative humidity for approximately 13 months prior to installation of the FRP wraps.

Fiber-reinforced polymer wraps

Because of their superior retention of mechanical properties at elevated temperatures (Bisby et al. 2002; Bisby 2003; Blontrock et al. 1999), carbon FRP was chosen as opposed to glass or aramid FRP as the wrap material for both columns. The FRP wrap design consisted of a single layer of a unidirectional carbon/epoxy FRP system with a 300 mm overlap in the circumferential direction and a 25 mm overlap in the vertical direction. The overlap lengths were chosen based on the industry partner's specifications, and their effects on the confined behavior of FRP-wrapped columns are not known (although they are not considered to be significant factors). The adhesive/matrix consisted of an epoxy.

The single-layer FRP wrap design was selected because it resulted in a theoretical ultimate load-capacity increase of approximately 53% based on ACI 440.2R-02 design guidelines, and of approximately 26% based on the ISIS (2001) guidelines. The larger theoretical increases in axial load capacity that could result from higher confinement ratios (with two layers of FRP, for instance) were thought to be unrealistic, and would not currently be practical in a design situation. Manufacturer-specified properties of the FRP and adhesive/matrix materials are given in Table 1.

Insulation schemes

A detailed review of the literature on the high-temperature behavior of FRP materials (Bisby 2003) indicated that rapid and severe deterioration of the mechanical and bond properties of FRP materials can be expected at only moderately increased temperatures, and highlighted the need for thermal insulation of FRP wraps. Until now, the approach used in the industry to provide insulation for FRP wraps has been to apply an intumescent paint to their exterior. In the event of a fire, the intumescent paint releases gases, foams, and expands to many times its original thickness, thereby forming an insulating char that protects the FRP from the thermal insult of the fire.

The primary shortcoming of intumescent systems for fire protection of FRP wraps is that the activation temperature (the temperature at which expansion and charring of the intumescent coating begins) for commonly available intumescent coatings is typically in the range of 200 to 300 ?C, substantially higher than the T^sub g^ of most FRP matrix polymers (matrixes T^sub g^ are typically between 65 to 150 ?C [ACI Committee 440 2002]). As a result, the mechanical properties of FRP wraps and/or the bond between the FRP and the substrate concrete are likely to be lost or seriously deteriorated before the onset of the intumescent reaction.

To improve the behavior of intumescent fire protection systems for use with FRP wraps, it was hypothesized that the addition of a secondary passive layer of insulation between the FRP and the intumescent coating would improve the fire endurance substantially. The rationale for this addition was that the intermediate layer, which would ideally consist of a passive layer of a highly insulating (low thermal conductivity and high heat capacity) and thermally inert material, would maintain the temperature of the FRP well below its T^sub g^ up until the onset of intumescence. After activation of the intumescent coating, the significant thermal insulation provided by the intermediate insulation, in combination with the intumescent char, would provide fire protection for the FRP for a substantial period of time.

With the aforementioned rationale in mind, a recently developed and innovative fire insulation system was selected for protection of both columns. The system is a two-component active/passive fire protection system. One component of the insulation is a modified cementitious vermiculite/gypsum plaster (VG), and the other, a surface coating, is an intumescent epoxy paint (EI).

For the columns tested herein, the VG insulation was first spray-applied over a galvanized steel plastering lath which was anchored to the outer surface of the FRP-wrapped columns using concrete anchors. The lath, which is not an essential component of the fire insulation system, was incorporated in these initial tests to provide a mechanical anchorage between the VG and the FRP and ensure that the insulation would remain intact for the duration of the tests. The lath was completely encased in VG insulation during the installation process. Column 1 was protected with approximately 57 mm, and Column 2 with approximately 32 mm. The EI epoxy surface coating was then hand-applied using a trowel to nominal thicknesses of 0.25 and 0.56 mm on Columns 1 and 2, respectively. Details of the insulation system are shown in Fig. 2.

Instrumentation

Both columns were extensively instrumented with thermocouples at their midheight, as shown in Fig. 2. In addition to the sensors installed within the columns, load and stroke were monitored by the load frame throughout the tests, and furnace temperatures were continuously monitored at eight different locations within the test chamber.

Test procedures

Both columns were tested by exposing them to heat in the column furnace at NRCC, which was built specifically for testing loaded full-scale columns under exposure to fire. The furnace, which is unique in North America, can reproduce the temperature, load, and heat transfer conditions to which a member might be exposed during a building fire. A detailed description of the test furnace is provided by Lie (1980).

The tests were carried out with both ends of the columns fixed against rotation and horizontal translation (a fixed-end condition). A concentric sustained axial load of 2515 kN was applied to both columns during fire exposure in accordance with ASTM E 119 specifications. ASTM E 119 states that, throughout a fire endurance test, a column shall be exposed to fire on all sides and shall be loaded in such a manner as to develop, as nearly as practicable, the working (service) stress contemplated by the design. In conventional cases (that is, for steel-reinforced concrete or structural steel columns), the sustained fire test load is determined by calculating the ultimate design strength of the member in question and, assuming some ratio of dead-to-live load (typically between 0.25:1 and 3:1), back-calculating the service load. A complication that arises for FRP-wrapped columns is considerable uncertainty as to what the design load capacity of the column should be because various design recommendations are currently available for FRP-wrapped columns. Current design recommendations (ISIS 2001; ACI Committee 440 2002) yield substantially different design strengths for FRP-wrapped columns, and a judgment call must therefore be made as to which set of recommendations to follow. In the present study, the design strength was calculated according to ISIS (2001), and the service loads were back-calculated from this value assuming a dead-to-live load ratio of 1:1, and using load factors of 1.5 for live load and 1.25 for dead load (Canadian Standards Association 1994). If the ACI 440.2R-02 design guidelines were used in combination with load factors of 1.4 and 1.7 for dead and live loads respectively, this would result in a service load of 3288 kN.

Table 2 provides a comparison of results of load calculations for the columns with respect to predicted failure load, ultimate design load, and service load for the FRP-wrapped and unwrapped cases using the ACI and ISIS design guidelines.

The load was applied to the columns for approximately 45 minutes before the start of the fire endurance tests, and was maintained at a constant value for the first 5 hours of fire exposure. After 5 hours, the applied load was gradually increased until failure occurred in an effort to obtain information that could be used to validate the numerical models, described as follows.

The fire exposure for the columns was simulated by controlling the average temperature in the furnace such that it followed, as closely as possible, the standard fire timetemperature curve of ULC S101 (Canadian Standards Association 1989), which is equivalent to ASTM E 119.

NUMERICAL MODEL

Because full-scale fire endurance tests are timeconsuming and expensive, a numerical model was developed by the authors such that, once validated by relatively few laboratory tests, it could be used to conduct parametric studies and investigate the effects of a number of parameters on the fire endurance of FRP-wrapped reinforced concrete columns. The specifics of the numerical model have been presented in a previous paper (Bisby 2003), so only a general overview is provided herein.

The model was developed using procedures and methodologies similar to those used previously by researchers at NRCC for modeling the fire endurance of conventionally reinforced concrete columns (Kodur and Lie 1997; Lie 1992; Lie and Celikkol 1991). The approach consists of a coupled heat transfer/load capacity analysis that has been programmed for a computer. The first portion of analysis uses an explicit finite-difference heat transfer formulation, based on an elemental energy balance, to calculate the temperatures inside a radially discretized column when it is subjected to a standard time-temperature curve. The heat transfer analysis accounts for the variation in thermal properties of the materials involved with temperature, and assumes that the column is infinitely long and the effect of internal reinforcing steel on heat transfer within the member can be neglected. The current model ignores the presence of the intumescent (EI) fire protection because the effects of the intumescent coating were relatively short-lived during the fire tests reported herein and are not thought to be significant. The second portion of the analysis calculates the load capacity of the member during fire, based on strain compatibility and equilibrium of forces, and on the known distribution of internal temperatures obtained during the heat transfer analysis.

The numerical model is unique in that it accounts for the confining effect of an FRP wrap in calculating the load capacity and elongation of a reinforced concrete column during fire, with failure occurring by buckling or by crushing of the concrete. The model incorporates a modified version of the iterative FRP confinement procedure developed by Spoelstra and Monti (1999), where the procedure has been modified to account for the deterioration in mechanical properties (and thermal expansion) of concrete, steel, and FRP with increasing temperature. The model does not currently account for the confining effect of the internal steel spiral. The output consists of the distribution of temperatures throughout the column cross section during exposure to fire, the variation in load capacity of the column, and the axial elongation of the column under a user-specified sustained load. A more complete description of the model is presented by Bisby (2003).

FIRE TEST RESULTS

Both columns behaved similarly during fire endurance tests, and both achieved greater than a 5-hour fire endurance rating according to ASTM E 119 guidelines. The unique two-component fire insulation performed well and remained intact for the duration of the tests. Failure of the columns occurred near the column midheight after 5.5 hours of exposure to fire, and failure was sudden and explosive. Failure appeared to occur by a combined buckling/crushing failure accompanied by violent spalling of the concrete cover and insulation. A failed column is shown in Fig. 3. It is important to recognize that failure of the columns occurred after prolonged exposure to fire, and only when the applied load on the columns was increased to approximately 180% of the required service load. The load was increased to determine the ultimate strength of the members at the end of the tests. The observed failure load of the columns after exposure to the standard fire for longer than 5 hours was slightly more than the predicted strength of the unwrapped columns calculated using either the ACI 318 (ACI Committee 318 1995) or CAN/CSA A23.3-94 (CSA 1994) codes without reduction factors.

Temperatures

Figure 4 shows temperature profiles recorded at several instructive locations in Column 1 during exposure to fire. Included in Fig. 4 are thermal profiles showing the standard fire curve (furnace temperature) along with the temperatures at the outside surface of the VG insulation, the outside surface of the FRP wrap, and the outside surface of the concrete.

The temperature at the surface of the VG insulation rose rapidly within the first 30 minutes of fire exposure, following the furnace temperature profile with a slight lag, to temperatures in excess of 600 ?C. It is interesting to consider that an unprotected FRP wrap would deteriorate completely at these temperatures. The VG insulation surface temperature then began to level off as the slope of the standard fire curve decreased.

Examination of the thermal profile at the surface of the FRP wrap in Fig. 4 and 5 indicates that good thermal protection for both columns was provided by the fire insulation system. The temperatures recorded at this location increased within the first hour of exposure, to temperatures between 95 and 100 ?C. The FRP surface temperature, however, then leveled off near 100 ?C for approximately 3 hours before increasing again beyond 4 hours of fire exposure. This plateau, near 100 ?C, is associated with the unique thermal properties of the fire insulation materials and is due to the release of both free and chemically combined water at temperatures close to 100 ?C. In combination with the very low thermal conductivity of the intermediate insulation, this moisture loss maintains the wrap temperature near 100 ?C for approximately 3 hours, and results in an insulation system that is extremely effective at maintaining low temperatures in the FRP wrap.

The thermal insulating ability of the FRP wrap can be approximately ascertained by examining the temperatures at the surface of the concrete in comparison with those at the surface of the FRP. Although FRPs generally have low thermal conductivities in the transverse direction (Bisby, Greene, and Kodur 2001), they are typically very thin in comparison with the insulation or the underlying concrete column. The data presented in Fig. 4 show that the concrete surface temperature closely followed the FRP surface temperature for Column 1. The magnitude of the temperature differential across the FRP increased late in the fire endurance test-behavior that was observed in both fire tests and appeared to be due to changing thermal properties of the wrap at elevated temperature, likely resulting from partial combustion of the FRP polymer matrix.

Temperatures recorded in the concrete and at the level of the internal reinforcing steel were observed to remain less than 120 ?C for the full 5.5 hours fire exposure for Column 1. It should be noted that such modestly increased temperatures are not significant for concrete or conventional steel reinforcement because there is no substantial loss in the strength of these materials up to temperatures of approximately 300 ?C. Thus, it can be stated that Column 1 likely maintained its full unwrapped strength for the entire duration of fire exposure. This conclusion is supported by the observed ultimate failure load of the column, discussed as follows.

Figure 5 shows temperature profiles recorded at various locations within Column 2 during exposure to fire. Again, the temperature at the surface of the insulation followed the standard fire curve, as expected, although more closely in this case than for Column 1. This can be attributed to uncertainty as to the exact location of the insulation surface thermocouples, which may have been slightly dislocated during installation of the insulation system. Thermal profiles recorded at the FRP and concrete surfaces were similar to those observed for Column 1, with the exception that the 100 ?C temperature plateau was reached earlier and was considerably shorter in duration for Column 2. This can be attributed to the fact that Column 2 was protected with approximately half the thickness of fire insulation applied to Column 1. Although significantly higher temperatures were experienced at the level of the FRP for Column 2, temperatures recorded in the concrete and internal reinforcing steel remained low (less than 200 ?C in this case), and thus the column likely maintained its full unwrapped strength for the entire duration of fire exposure.

Axial deformation

Figure 6 shows the axial deformation of both columns recorded during fire exposures. Both columns displayed a very slight elongation under fire exposure as a consequence of very mild thermal expansion. The magnitude of the expansion was greater for Column 2, which experienced slightly higher internal temperatures than Column 1 due to a lower thickness of insulation. The overall magnitude of the columns' expansion was small in comparison with their overall length, with a maximum observed elongation of less than approximately 0.025% of the original length (3810 mm). This can be attributed to the beneficial thermal insulation provided by the fire protection, which resulted in minimal temperature increases in the concrete and internal reinforcing steel.

Beyond 5 hours of fire exposure, both columns displayed a sudden and severe contraction, which can be attributed to increasing the applied load at 5 hours up until failure.

Fire endurance

Table 3 provides fire endurance times for both columns based on the three potential fire endurance failure criteria outlined previously. As stated previously, both columns achieved fire endurances longer than 5 hours based on ASTM E 119 load capacity criterion (Criterion 1).

If the fire endurance of the columns is defined in terms of the time to reach the matrix T^sub g^ (which was approximately 93 ?C for the FRP system discussed herein), then Columns 1 and 2 have fire endurances of 182 and 82 minutes, respectively. These times are less than the ones based on the structural fire endurance criterion (Criterion 1), and illustrate that it is indeed overly conservative to define fire endurance in terms of the matrix T^sub g^.

Based on failure Criterion 3, exceeding the ignition temperature of the FRP polymer matrix, both columns displayed fire endurances longer than 5 hours, and combustion of the FRP wrap does not appear to be a serious concern for either of the columns tested.

MODEL VALIDATION

The numerical model, described very briefly in a previous section and in detail by Bisby (2003), has been previously validated against data obtained from fire tests on unwrapped and uninsulated circular reinforced concrete columns (Bisby 2003). In the following discussion, data obtained from the two fire endurance tests described herein are used to validate the model for the FRP-wrapped and insulated case.

Temperatures

Figure 4 and 5 show comparisons of experimental data and model predictions for temperatures at several locations for Columns 1 and 2, respectively. In Figure 4 and 5, the predicted temperatures at the FRP surface and concrete surface are essentially coincident. In both cases, the model predictions agree relatively well with the experimental data, and the model accurately captures the overall trends observed in the test data. The model does not, however, precisely capture the 100 ?C temperature plateau observed in the test data at the surfaces of the FRP and the concrete. This can be explained by considering that the model does not explicitly account for the evaporation of moisture from the insulation at 100 ?C, nor does it account for moisture movement within the insulation (which tends to cause moisture to move toward the center of the column, away from the heat source). The model accounts for moisture evaporation in the insulation by artificially increasing the specific heat of the insulation elements at temperatures near 100 ?C, an approach that has been used successfully in the past. While capturing the 100 ?C plateau is not critical for calculating the structural fire endurance of the FRP-wrapped columns, it could become important if fire endurance is defined in terms of the matrix T^sub g^ because T^sub g^ is close to 100 ?C for many currently available FRP-wrap matrix materials. The model appears to overpredict the temperature at the surface of the VG insulation early in the fire tests. This behavior can be attributed to the fact that the temperatures at the surface of the VG insulation are reduced by the action of the intumescent EI coating during the first 15 to 20 minutes of fire exposure, behavior which is not accounted for in the model but which is relatively short-lived and not thought to be significant for the overall fire endurance of the columns.

Figure 5 also shows that the numerical model underpredicts the temperatures at the level of the FRP wrap beyond 80 minutes of fire exposure for Column 2. This discrepancy is thought to be due to the development of cracks in the insulation, which were observed to gradually appear and widen as the fire endurance tests progressed, and which could have allowed heat to penetrate more rapidly to the level of the FRP. Cracking of the insulation is not accounted for in the model.

Figure 7 shows predicted and observed temperatures at the level of the internal reinforcing steel for Column 1. The figure includes curves for temperatures recorded on the steel spirals and on the vertical reinforcing bars on the side of the bar closest to the fire (outside) and the side of the bar furthest from the fire (inside). Satisfactory agreement between test data and model predictions is evident, particularly given that the reinforcing steel temperature remained less than 100 ?C for the duration of fire exposure. Similarly, good agreement between test data and model predictions was noted for Column 2 at the level of the internal reinforcing steel.

Load capacity

The ability of the numerical model to predict the loadcarrying capacity of FRP-wrapped columns during fire is an important consideration in its validation. Figure 8 shows the predicted load capacity of Columns 1 and 2 under exposure to fire, together with curves showing the applied load on both columns during tests. It is important to recognize that because the load capacity analysis approximates the buckling strength on the member, for the numerical model to function properly, an initial eccentricity is required as input. In the development of Fig. 8, an initial eccentricity of 27 mm was chosen, in accordance with Section 10.12.3.2 of ACI 318-95. Although the analysis is also capable of predicting the axial crushing strength of the columns during fire, the bucklingtype failure governs the design for column lengths that would generally be encountered in practice.

As expected, the model predicts that the axial load capacity of the columns deteriorates only slightly during exposure to fire. This can be attributed to the beneficial thermal protection provided by the insulation, primarily to the concrete and reinforcing steel. It remains unknown as to whether the wrap remained effective in the later stages of the tests. The model predictions for failure load agree well with test observations even after 5.5 hours of exposure to the ASTM E 119 standard fire. Thus, it appears as though the model can accurately predict the failure load and structural fire endurance of FRP-wrapped and insulated columns, although further tests are required to confirm this initial conclusion.

Axial deformation

Figure 6 shows the measured and predicted axial deformations of Columns 1 and 2 as a functions of fire exposure time, assuming an applied axial load of 2515 kN, as was applied during the fire tests. The model tends to overpredict the expansion of both columns for the full length of fire exposure. Nonetheless, the largest difference between predicted and measured axial deformation is on the order of 1.5 mm, which is small in comparison to the overall length of the columns.

For the design of structures for fire safety, the model is conservative because larger axial deformations in fire would result in the development of larger induced deflections in a structure. It is suspected that the discrepancy between the predicted and observed column deformations can be attributed primarily to short-term creep of the concrete at elevated temperatures in combination with some minor seating effects. Given the extremely small magnitude of the deformations, both predicted and observed, it is difficult to state conclusively whether the model is an adequate predictor of axial elongation for FRP-wrapped and insulated columns.

DISCUSSION

One interesting question that arises in any discussion of the fire tests described in this paper is whether the FRP wrap remained effective for a significant period of time during fire. Unfortunately, it is not possible to state conclusively when, or if, the FRP wrap became ineffective as a confining mechanism for the concrete. It is known that FRP confinement is only significantly activated at stress levels close to the unconfined ultimate strength of the concrete. The sustained service load applied to the columns in the current study (2515 kN) would result in a concrete stress of only approximately 17 MPa during fire, significantly less than the ultimate strength of the unconfined concrete. Hence, no noticeable change in column behavior would be expected due to loss of the confining action of the FRP wrap.

It is important to recognize that the superior fire behavior of the FRP-wrapped and insulated columns described herein is due primarily to the thermal protection provided the insulation system to the concrete and reinforcing steel, and it is unlikely that the wrap remained effective toward the end of the tests. It could thus be argued that an unwrapped but insulated column would perform similarly in fire to an equivalent FRP wrapped and insulated column. However, columns are confined with FRP to increase their axial load capacity at ambient conditions, not to increase their structural fire endurance. Therefore, supplemental fire insulation is required in these cases to ensure that the overall column can safely carry the increased service loads in the event of fire. This is because fire safety engineering is concerned primarily with protection against structural collapse and loss of life during fire, and so it is the overall load-carrying capacity of the FRP-wrapped columns that is important, not the maintenance of the FRP confinement.

To illustrate the aforementioned points, Fig. 9 shows the variation in load capacity of an FRP-wrapped and insulated column (Column 2) as predicted by the numerical model, along with an equivalent unwrapped column and FRPwrapped but uninsulated column. Also included in Fig. 9 are horizontal lines showing the calculated service loads on these columns according to ACI 318 and ACI 440 (assuming a live to dead load ratio of 1.0). The initial strength of the wrapped columns is only slightly increased because the columns are assumed to fail by buckling, which is the critical failure mode during fire, and FRP confinement cannot be expected to significantly increase the columns' buckling strength.

The unwrapped column has a predicted fire endurance of about 245 minutes, whereas the wrapped but uninsulated column, which has an increased service load, is predicted to fail at 100 minutes This highlights the need for supplemental fire insulation to achieve similar fire endurance for the FRPwrapped column. Indeed, by insulating the column with 32 mm of the insulation system described previously, the fire endurance increases to longer than 6 hours. Thus, the predicted fire endurance for the FRP-wrapped and insulated column becomes greater than for the unwrapped column, even though the wrap likely becomes ineffective during fire exposure.

CONCLUSIONS

Based on the results of full-scale fire endurance tests on circular FRP-wrapped and insulated reinforced concrete columns, the following conclusions can be drawn:

1. The insulation system described herein is an effective protection system to maintain the overall load-carrying capacity of FRP-wrapped reinforced concrete columns during fire. The insulation remained intact for more than 5 hours of exposure to the ASTM E 119 fire;

2. It is possible, with the requisite thickness of the fire insulation, to maintain the temperature of an FRP wrap below 100 ?C for up to 4 hours during exposure to the standard fire;

3. Both of the FRP-wrapped and protected reinforced concrete columns described herein achieved fire endurance ratings in excess of 5 hours according to ASTM E 119, with service loads calculated using the ISIS Canada design guidelines (ISIS 2001); and

The predictions of a numerical fire endurance model, developed previously by Bisby (2003) to predict the heat transfer behavior and axial load capacity of FRP-wrapped and insulated reinforced concrete columns during exposure to fire, were compared with data obtained from the fire tests discussed herein. The following conclusions can be drawn on the basis of that comparison:

4. The numerical model can adequately predict temperatures within circular FRP-wrapped and insulated reinforced concrete columns during exposure to fire; and

5. The numerical model appears to be capable of predicting the load capacity and structural fire endurance of FRP-wrapped and insulated reinforced concrete columns.

Both the fire endurance tests and the numerical model indicate that the fire endurance of FRP-wrapped concrete members should be determined using a holistic approach, with the goals of fire-safety engineering clearly in mind. Thus, structural fire endurance should be defined on the basis of load-carrying capacity, rather than other possible criteria such as the T^sub g^ of the FRP polymer matrix/adhesive or the effectiveness of the FRP wrap. FRP-wrapped columns treated in this manner are capable of achieving required fire endurance, provided that insulation is applied to the exterior of the FRP wrap.

ACKNOWLEDGMENTS

The authors are members of the Intelligent Sensing for Innovative Structures Network (ISIS Canada) and wish to acknowledge the support of the Networks of Centres of Excellence Program of the Government of Canada and the Natural Sciences and Engineering Research Council of Canada. The authors would also like to acknowledge the National Research Council of Canada, Queen's University, Kingston, Ontario, Canada, and Fyfe Co. LLC, San Diego, Calif.

REFERENCE

REFERENCES

ACI Committee 440, 2002, "Guide for the Design and Construction of Externally Bonded FRP Systems for Strengthening Concrete Structures (ACI 440.2R-02)," American Concrete Institute, Farmington Hills, Mich., 45 pp.

ACI Committee 318, 1995, "Building Code Requirements for Structural Concrete (ACI 318-95) and Commentary (318R-95)," American Concrete Institute, Farmington Hills, Mich., 369 pp.

ASTM E 119-00a, "Standard Methods of Fire Test of Building Construction and Materials," ASTM International, West Conshohocken, Pa., 2000, 21 pp.

Bisby, L. A., 2003, "Fire Behaviour of Fibre-Reinforced Polymer (FRP) Reinforced or Confined Concrete," PhD thesis, Department of Civil Engineering, Queen's University, Kingston, Ontario, Canada, 371 pp.

Bisby, L. A.; Green, M. F.; and Kodur, V. K. R., 2001, "Fire Behaviour of FRP-Wrapped Reinforced Concrete Columns," Structural Faults and Repair-2001, London, July. (CD-ROM)

Bisby, L. A.; Williams, B. K.; Green, M. F.; and Kodur, V. K. R., 2002, "Studies on the Fire Behaviour of FRP Reinforced and/or Strengthened Concrete Members," Proceedings of the 2nd International Conference on the Durability of Composites for Construction, Montreal, Quebec, Canada, May, pp. 405-417.

Blontrock, H.; Taerwe, L.; and Matthys, S., 1999, "Properties of Fiber Reinforced Plastics at Elevated Temperatures with Regard to Fire Resistance of Reinforced Concrete Members," Fourth International Symposium on Fiber Reinforced Polymer Reinforcement for Reinforced Concrete Structures, SP-188, C. W. Dolan, S. H. Rizkalla, and A. Nanni, eds., American Concrete Institute, Farmington Hills, Mich., pp. 43-54.

Blontrock, H.; Taerwe, L.; and Vandevelde, P., 2000, "Fire Tests on Concrete Beams Strengthened with Fibre Composite Laminates," Third PhD Symposium, Vienna, 10 pp.

Blontrock, H.; Taerwe, L.; and Vandevelde, P., 2001, "Fire Testing of Concrete Slabs Strengthened with Fibre Composite Laminates," Proceedings of the Fifth Annual Symposium on Fibre-Reinforced-Plastic Reinforcement for Concrete Structures (FRPRCS-5), Thomas Telford, London, pp. 547-556.

CAN/CSA G30.18, 1992, "Billet-Steel Bars for Concrete Reinforcement," Canadian Standards Association, Mississauga, Ontario, Canada, 18 pp.

CAN/ULC, 1989, "Standard Methods of Fire Endurance Tests of Building Construction and Materials," CAN/ULC-S101-M89, Underwriters' Laboratories of Canada, Scarborough, Ontario, Canada, 49 pp.

CSA, 1994, "Design of Concrete Structures (CAN/CSA A23.3-94)," Canadian Standards Association, Ottawa, Ontario, Canada, 220 pp.

ISIS, 2001, Strengthening Reinforced Concrete Structures with Externally Bonded Fiber Reinforced Polymers, Intelligent Sensing for Innovative Structures Canada, Winnipeg, Manitoba, Canada, 193 pp.

Kodur, V. K. R., 1999, "Fire Resistance Requirements for FRP Structural Members," Proceedings of the Annual Conference of the Canadian Society for Civil Engineering, Regina, Saskatchewan, Canada, pp. 83-95.

Kodur, V. K. R., and Baingo, D., 1998, "Fire Resistance of FRP Reinforced Concrete Slabs," IRC Internal Report No. 758, National Research Council of Canada, Ottawa, Ontario, Canada, 37 pp.

Kodur, V. K. R., and Lie, T. T., 1997, "Evaluation of the Fire Resistance of Rectangular Steel Columns Filled with Fibre-Reinforced Concrete," Canadian Journal of Civil Engineering, V. 24, No. 3, pp. 339-349.

Lie, T. T., 1980, "New Facility to Determine Fire Resistance of Columns," Canadian Journal of Civil Engineering, V. 7, pp. 551-558.

Lie, T. T., 1992, "Structural Fire Protection," Manuals and Reports on Engineering Practice No. 78, ASCE, New York, 241 pp.

Lie, T. T., and Celikkol, B., 1991, "Method to Calculate the Fire Resistance of Circular Reinforced Concrete Columns," ACI Materials Journal, V. 88, No. 1, Jan.-Feb., pp. 84-91.

Munley, E., and Dolan, C. W., 2001, "What is the Value of it All?" Proceedings of the Fifth Annual Symposium on Fibre-Reinforced-Plastic Reinforcement for Concrete Structures (FRPRCS-5), Thomas Telford, London, pp. 585-592.

Sorathia, U.; Dapp, T.; and Beck, C., 1992, "Fire Performance of Composites," Materials Engineering, Sept., pp. 10-12.

Spoelstra, M. R., and Monti, G., 1999, "FRP-Confined Concrete Model," Journal of Composites for Construction, V. 3, No. 3, pp. 143-150.

AUTHOR_AFFILIATION

ACI member Luke A. Bisby is an assistant professor of civil engineering at Queen's University, Kingston, Ontario, Canada. He received his BEng in civil engineering from McGill University, Montreal, Quebec, Canada, in 1997 and his MSc (Eng.) and PhD in civil engineering from Queen's University in 1999 and 2003, respectively. He is a member of ACI Committee 440, Fiber Reinforced Polymer Reinforcement, and Joint ACI-TMS Committee 216, Fire Resistance and Fire Protection of Structures. His research interests include reinforcing and strengthening reinforced concrete structures with fiber-reinforced polymers, with an emphasis on fire behavior.

ACI member Venkatesh K. R. Kodur is a professor in the Department of Civil and Environmental Engineering at Michigan State University, East Lansing, Mich. He is a member of ACI Committees 440, Fiber Reinforced Polymer Reinforcement, and 544, Fiber Reinforced Concrete. He is also a member and Secretary of Joint ACI-TMS Committee 216, Fire Resistance and Fire Protection of Structures.

ACI member Mark F. Green is a professor of civil engineering at Queen's University. He received his BSc from Queen's University and his PhD from Cambridge University, UK, in 1991. He is a member of ACI Committee 440, Fiber Reinforced Polymer Reinforcement. His research interests include strengthening concrete structures with fiber-reinforced polymers, prestressing concrete beams with fiber-reinforced polymers, and bridge-vehicle dynamics.