Corrosion problems.

By Krogstad, Norbert V.
Publication: Masonry Construction
Date: Friday, July 1 2005

Q In examining masonry lintels on the top floor of a building, I noticed that instead of the brick being supported directly on the angle, there was a gap of almost 1/2-inch between the bottom of the brick and lintel in many locations. In fact, it seemed that the brick was not even being supported

by a lintel at all, except for several isolated spots where there appeared to be some kind of shim filling the gap between the bottom of the brick and the angle.

The "shims" were brown in color and had a very rough texture and a layered appearance. The angles were severely corroded. In some cases, the remaining thickness of the angle was less that 3/16 inch. The bed joint in the masonry between these windows was very wide and appeared to have been pointed, indicating that the masonry moved upward.

What caused this gap?

A Without seeing the condition, it is difficult to know exactly what occurred; however, I have seen a condition similar to what you described. In that case, the gap was caused by corrosion of the steel angle.

When steel corrodes, the resulting rust scale occupies more space than the steel. In fact, the corrosion byproducts can be 10 times greater than the volume of the steel that is corroding. The corrosion lifts the masonry above the lintels (sometimes exceeding 1 inch.). This action is often referred to as "rust jacking."

Depending on the exposure, it is possible that the corrosion product has washed or fallen out of the joints, leaving only isolated portions of rust scale to support the masonry wall. A roof leak or some other directed water flow moving through the wall system may--over time--carry away the rust scale.

If the gap is caused by rust jacking, the lintel angles likely have significant pitting of the steel. Depending on the magnitude of this corrosion or pitting, the angles may need to be replaced with new steel versions. This change can be accomplished by first shoring masonry above the lintels so that they can be removed and replaced. The angles should be covered with a proper flashing and weep system to direct any water that penetrates the masonry back to the exterior, and to prevent water from reaching the surface of the angles, thereby reducing the corrosion rate.

The movement may have damaged ties between the veneer wythe and the backup. This possibility is especially the case if the wythes are tied using brick headers. The stability of the wall should be evaluated. If the bonding between the wythes has been compromised, remedial anchors can be installed through the veneer wythe. These anchors are generally installed in the "T" joint created by the intersection of the head and bed joints, as shown in the illustration. The hole created is pointed following the installation of the anchors.

Norbert V. Krogstad is a consultant at Wiss, Janney, Elstner Associates Inc., Northbrook, Ill.

In addition, make sure to read these articles:

  • Damage strategies.
  • Preplanning and fast response help recover more than you might expect. After an incident resulting in physical properly damage occurs, a proper and thorough site/damage ......
  • Repairing concrete balconies.
  • Whether sipping morning coffee, reading a favorite novel, or soaking in some sun, most people tend to make good use of their balconies without a ......
  • Roofing: Repair, recover or replace?
  • HEADNOTE Facility executives must understand the condition of the roof to determine which choice makes the best economic sense MANY BUILDING OWNERS and facility executives ......
  • Shelf angle problems.
  • Q How do you prevent thermal shorts in shelf angles? Can anything be done to eliminate the heat loss at these angles? A I am ......
  • Bringing ideas to market: now more than ever, companies must focus on innovation. In this...
  • Q. Innovation is always important in business, but haven't a lot of companies been putting it on the back burner over the past year in ......
  • Grinding joints for repointing.
  • Q What is a good way to grind out joints for repointing glazed brick masonry? I am afraid that I will chip off the glaze ......
  • Q&A: chief fire officer Peter Holland.
  • Q: What aspect of modernisation do you believe is the most important? A: There can only be one answer to this question. We are now ......
  • How experts approach catastrophic structural and building failures
  • HEADNOTE Experienced technical experts will be able to meet and overcome many of the obstacles that may tend to impair their investigations IN JUNE 1981, ......
  • Affects of torching.
  • Q Masons doing residential construction work occasionally use a torch during cold weather to speed up the drying or settling of the masonry. Besides some ......
  • Elstner Associates Inc.
  • Professional firm provides practical, innovative, and technically sound solutions to structural, architectural, and materials problems. Serving thousands of clients, from individuals to large corporations and ......
  • Installing flashing over arched windows.
  • Q How do you install flashing at an arched opening over a window? This situation is a particular problem if the window is installed after ......
  • WJE
  • Bruce McMahon has joined Wiss Janney Elstner Associates, Inc. as a senior associate in the Dallas office. McMahon brings to WJE more than 23 years ......
  • Toothing considerations.
  • Q Toothing of the masonry is not permitted in many architectural specifications. Why does toothing provide less strength than raking or stepping back the masonry ......
  • Using raked mortar joints.
  • Q Many references strongly recommend using tooled mortar joints rather than raked joints. On many projects, however, raked joints are needed to match the historic ......
  • LGA Thin Film RF Inductor Provides Tight Tolerances, High Q in Small Case Size.
  • Miniature Thin Film RF Inductor Offers Superior High Frequency Performance MYRTLE BEACH, S.C. -- Based on thin-film multilayer technology, AVX Corporation has developed an 0402 ......