Laboratories are the third-most energy-intensive building type. A single fume hood can consume as much energy as three single-family homes. But different types of labs can exhibit wide variations in energy needs, which often discourage designers from trying to make their laboratories energy efficient.

Moreover,

many lab designers use either estimates based on rated data, or design benchmarks from prior projects. Consequently, peak equipment loads are frequently overestimated by anywhere from 40 to 300%, according to a Syska Hennessy Group study.

"There has to be a way of looking at this and analyzing it with some mathematics that makes sense," said John "Jay" Martin, PE, a design engineer in the San Diego office of Syska Hennessy.

"When it comes to planning and sizing HVAC and piped-utility systems, the current methods are no better than guesses," said Martin, who has overseen hundreds of laboratory projects in his more than 30 years as a mechanical engineer.

One source of error is benchmarking databases. These are collections of heat gain values categorized by laboratory space type over a number of different projects or project types, as compiled by laboratory consultants and programmers. These numbers are used to size new laboratory HVAC systems. In a 2004 study, Martin estimated the cost of over-sizing HVAC systems due to benchmarking was at least $7.50/sf, possibly double or triple that.

"The problem lies in the fact that the calculation of the heat gain generated in any laboratory space by these databases is extremely flawed," said Martin.

Benchmarking frequently results in oversized HVAC systems because the databases use peak demand data—and assume that all systems will be used simultaneously in the laboratory. The engineers then guess at a value higher than the quoted average of the peak demand numbers that will satisfy the spaces with the highest heat gain. This leads to a situation where laboratory spaces that don't need maximum ventilation and conditioning are being designed for the peak load.

One promising method to help fight oversizing lab systems is probability-based analysis, or PBA.

PBA derives diversity factors of space loads, rather than maximum peak loads, using the centuries-old mathematic application of probability. "PBA is actually hundreds of years old," Martin explained. "This is really nothing new."

More than 70 years ago, in fact, Dr. Roy B. Hunter used PBA to determine peak water flow demand in plumbing systems. Hunter's curves determined the probability of any of a number of fixtures to demand water at any given time.

PBA does the same thing for laboratory spaces. By using Hunter's equation, engineers can create curves that show the aggregate probability of use for each heat source in a space. PBA and building load measurements can then be used together, providing two reference points for rightsizing.

PBA can calculate the diversity factors of different levels of aggregation—for example, as the number of pieces of lab equipment goes up, so, too, does the number of variables. It has been used in the design of a number of labs, including the new UCLA Life Sciences Center. The extra cost of PBA, according to Martin, is $.50/sf, compared to the average $7.50/sf he estimates current oversizing is costing lab owners.

Metering is another tool being used to rightsize laboratory buildings. UC Riverside measured equipment loads at two of its laboratories in order to use the data as a basis for sizing HVAC systems in the design of new facilities there.

"Metering is certainly a step in the right direction, but the question then becomes, how long are you going to meter?" Martin asked. "What we really need is proven scientific methods to base sizing on, and that's what PBA is."

For more on PBA, read Jay Martin's "A Case for Probability Based Analysis": www.bdcnetwork.com/contents/pdfs/bdc0603PBAWhitepaper.pdf .

How to calculate PBA

  1. For each type of heat source in a space, determine the number of sources and their outputs. This could be based on pieces of equipment or the number and type of electrical and other outlets (as a proxy for peak equipment output). This information is often available from programming documents.

  2. For each type of heat source in a space, determine the likelihood that it will be used. This data can be obtained through empirical measurements and surveys.

  3. Use probability formulae to calculate the peak simultaneous load for the space, using the PBA equation for each heat source.

In addition, make sure to read these articles:

  • Choosing a Budget Method
  • A budget is nothing more than a written estimate of how an organization — or a particular project, department, or business unit — will perform ......
  • Futuremark Debuts PCMark04 for PC Performance Benchmarking; Application Based Benchmark...
  • Business Editors/High-Tech Writers SARATOGA, Calif.--(BUSINESS WIRE)--Nov. 25, 2003 Futuremark(R) Corporation, the leading provider of computer performance analysis software and services, today unveiled PCMark(TM)04, the latest ......
  • Consider the site in geothermal cooling
  • IMAGE ILLUSTRATION 1 With reliability provided by advances in construction techniques and materials, and the efficiency increases attributed to maturing mechanical and electronic technology, geothermal ......
  • Fresh air: New HVAC approaches
  • HEADNOTE HVAC HEADNOTE Building owners are looking closely at a RANGE OF INNOVATIONS as the marketplace demands change IMAGE ILLUSTRATION 3 The entire HVAC industry ......
  • Below the Surface
  • Geothermal experts share system specification tips for this ever-emerging, energy-efficient, sustainable technology. CONSULTING-SPECIFYING ENGINEER: It's been said that geothermal technology has been gaining popularity over ......
  • Updating lighting and HVAC systems can lower energy costs
  • Summer is fast approaching, and if the recent energy crisis in California is any indication, it could be a costly season that will push many ......
  • New demands, new opportunities
  • HEADNOTE Strategies exist to help today's HVAC systems meet increased needs - if you know where to look COMFORT AND CONTROL, flexibility, equipment loads, energy ......
  • Window Film Reduces Overheating and Enhances Aesthetics.
  • Solar heat gain through existing glass was a serious problem at the Washington, D.C. headquarters of the American Institute of Architects (AIA). Few realize that ......
  • Notes From the Log of a LEED Navigator: Pt. 2
  • The pursuit of a gold or platinum LEED-certified building often requires the implementation of cutting-edge systems. This certainly was the case with Pittsburgh's David L....
  • Sizing systems for savings
  • HEADNOTE HVAC efficiency starts with knowledge of facility systems, building use IMAGE ILLUSTRATION 2 Facility executives wouldn't think of lighting an office cubicle with a ......
  • Evaluating HVAC and the Building Envelope
  • In this article, we will look at how to design HVAC and building envelope systems for their optimum use. We'll also evaluate HVAC and building ......
  • HVAC systems. (The Guide).
  • Designed to handle dehumidification in applications requiring handling 150 cfm to 1,000 cfm, units in the DryLine 2001 product line can stand-alone or be used ......
  • CLOSING GAPS IN HVAC DESIGN
  • HEADNOTE Four steps can help facility executives ensure that KEY EFFICIENCY PRINCIPLES are at the core of the HVAC system design For most facility executives, ......
  • When Size Matters
  • When doing an addition or renovation, remodelers often have to reconfigure or even replace the home's heating, ventilation and air conditioning (HVAC) system. If you ......